Quick Links TOC

One Canal Place

  Fire Alarm System

OPERATION

When the fire alarm system is activated, the following automatic functions take place in the building:

  1. The alarm will sound on the emergency floor plus the floor immediately above and immediately below the emergency floor.
  2. An alarm will activate in the building’s Central Control Station.
  3. The pressurization fans in the stairwells will pressurize the stairwells.
  4. The elevators will proceed non-stop to the first floor main lobby and, upon arrival, the elevator doors will open and remain open until reset by building personnel or the Fire Department. (NOTE: ELEVATORS ARE NOT TO BE USED IN AN EMERGENCY EVACUATION).
  5. Stairwell doors will unlock to provide ingress and egress.
View Full Site Suggestion Box
© 2024
All rights reserved.